97狠狠狠狼鲁亚洲综合网,国产亚洲欧美另类一区二区三区,亚洲狠狠操,国产美女做爰免费视频,亚洲第一av,青青草啪啪啪网站在线观看,国产精品一区二区无线 ,男人午夜视频在线观看免费
            English | 中文     BAC Global :
            Home > Products & Services > Ice Thermal Storage > District Cooling

            District Cooling

            2.Benefits

            Date : 2013-10-21 00:17
            QWhy Ice Thermal Storage for District Cooling Projects?
            ABecause only ice, on a simple and practical basis, can provide a constant 34°F (1°C) supply fluid temperature that yields:
            1. Lowest first cost system that does not require utility incentives
            2. Reduced energy costs by providing flexibility in when energy is used and reducing the total system kWh usage
            3. Reduced maintenance by using smaller equipment with flexibility in service schedules
            4. Improved system reliability ensuring constant cooling
            5. Space savings with reduced equipment room and heat rejection requirements
            6. Environmentally friendly systems with reduced energy consumption and global warming

            ?填充圖片

            Lowest First Cost

            image002image004
            An ice storage system that takes advantage of low temperature fluid is the lowest first cost design. Substantial savings in the chilled water distribution system are realized when the system design incorporates reduced flow rates that result from using a larger temperature range in the water loop. Use of a 20°F (11°C) temperature range instead of a conventional 10°F (5.6°C) to 14°F (7.8°C) temperature range results in a substantial reduction in pipe size. Smaller distribution piping can often be installed via trenching versures tunneling, allowing the piping to be installed with less time and expense.
            The savings that result from the use of smaller distribution piping offset the cost of the thermal storage equipment. A 16,000 ton (5,632 Mw) district cooling plant designed with centrifugal chillers using 44°F (7°C) supply water and one with ice storage using 34°F (1°C) supply water were compared. The conventional plant required 30in (762 mm) diameter distribution piping ($7,680,000 installed) versus 18in (457 mm) for the ice storage system ($5,340,000 installed) that yielded savings of $2,340,000.

            Cost

            44°F (7°C) Supply Water System

            34°F (1°C) Supply Water System

            Chiller Equipment

            2,960,000

            2,865,000

            Cooling Towers $ Evaporative Condensers

            623,725

            588,838

            Pumping Equipment

            551,905

            402,106

            Thermal Storage Equipment

            N/A

            2,957,920

            Equipment Rigging

            206,781

            289,666

            Mechanical Piping

            2,560,000

            2,711,200

            Mechanical Insulation

            844,800

            894,696

            Refrigerant

            224,800

            73,132

            Refrigerant

            224,800

            73,132

            Plant Ventilation

            16,733

            99,934

            Automation System

            993,218

            1,805,987

            Electrical Equipment

            2,475,742

            1,835,634

            Building Cost

            3,960,000

            2,645,775

            Sales Tax (Equipment & Material)

            600,138

            624,536

            CONSTRUCTION COSTS

            16,017,042

            624,536

            Project Management $ Engineering

            1,927,113

            2,053,249

            Project Contingency

            897,208

            995,401

            TOTAL PLANT COST

            16,017,042

            624,536

            Street Distribution Piping Cost Estimate

            6,000 Linear Feet: Trenching & Restoration

            5,820,000

            3,960,000

            12,000 Linear Feet of Supply and Return Piping

            1,860,000

            1,380,000

            TOTAL STREET PIPING COST

            7,680,000

            5,340,000

            Total Building Connections Cost Estimate

            Heat Exchangers

            960,000

            422,400

            Stations

            560,000

            480,00

            Piping, Erection & Insulation

            2,960,000

            1,977,600

            TOTAL BUILDING CONNECTION COST

            4,480,000

            2,880,000

            16,000 TON COOLING SYSTEM TOTAL

            31,001,363

            28,303,324

            ?填充圖片

            Reduced Energy Cost

            With smaller mechanical equipment, ice thermal storage can lower electrical demand charges up to 50%. In addition, total annual energy consumption is less because of the lower pumping horsepower (kW). As the electric industry continues to deregulate, and time-of-use rates, real time pricing schedules and negotiated power prices become standard, ice storage can provide even greater future savings in operating costs.
            In a comparison of a 16,000 ton (5,632 MW) district cooling plant designed with centrifugal chillers using 44°F (6.7°C) supply water and one with ice storage using 34°F (1°C) supply water, the peak demand was 15,985 kW for the conventional plant and 10,135 kW for the ice plant, a 37% reduction in peak demand.
            image005

            ?填充圖片

            Reduced Maintenance

            The ice storage coils have no moving parts so very little maintenance is required. The only ice thermal storage maintenance required includes the air pump, system fluid and controls. Because the chillers, pumps and heat rejection equipment are smaller, the ice storage system will have less maintenance than a conventional system.
            image010image008

            ?填充圖片

            Improved System Reliability

            image012 Ice Storage systems provide the reliability necessary to ensure air-conditioning is available. With conventional systems, installing multiple chillers provides redundancy. In the event of a mechanical failure of one chiller, the second chiller provides limited cooling capacity. The maximum available cooling for the conventional system would only be 50% on a design day.
            Most ice storage systems utilize two chillers in addition to the ice storage equipment. Two chillers are designed to provide approximately 60% of the required cooling on a design day while the ice storage provides the remaining 40% of the cooling capacity. In the event only one chiller is available to provide cooling during the day, up to 70% of the cooling capacity is available. The one operable chiller provides 30% of the cooling requirement while the ice provides up to 40%. Base on typical HVAC load profiles and ASHRAE weather data, 70% of the cooling capacity would meet the total daily cooling requirements 85% of the time.

            ?填充圖片

            Space Savings

            Ice Thermal Storage saves equipment room and heat rejection space since smaller chillers, pumps and heat rejection equipment is required. A district cooling plant with ice thermal storage requires two-thirds of the chiller and heat rejection capacity of a conventional system. The chilled water pumps will be half the size of a typical 10°F (5.6°C) temperature differential system, and the condenser water pumps will be two-thirds the size of a conventional system. The plan area required for the equipment room and heat rejection equipment can be cut by one-third. The thermal storage can be located outdoors, in a sub-basement or under a parking lot, it does not have to be part of the equipment room.

            Chilled water storage requires 4 to 10 times the space of ice thermal storage. The use of sensible cooling combined with storage inefficiencies make chilled water storage tanks larger.

            image014

            傳統(tǒng)系統(tǒng)的設(shè)備室

            image016

            填充圖片

            Environmentally Friendly

            image017 Reducing energy consumption and using electricity at night will reduce global warming. District cooling, using new energy efficient water-cooled chillers and ice storage, will significantly reduce energy consumption. Electricity generated at night generally has a lower heat rate (lower fuel use per power output), and therefore, lower carbon dioxide and greenhouse gas emissions resulting in less global warming.The California Energy Commission concluded that the use of electricity at night created a 31% reduction in air emissions over the use of electricity during the day. The use of an environmentally friendly and energy efficiency ammonia refrigerant, can be considered for may district cooling systems.
            ?